| Agency Approvals | : | UL 916; CE: EN61000-6-2, EN61000-6-3, EN61000 Series, immunity, EN 61326-1; FCC Part 15 Class A; REACH, RoHS, RoHS 2 (China), RCM (Australia), ICES-003 (Canada), UKCA (UK) |
| Application Zone | : | Plant Room |
| Brand | : | Veris |
| CO2 Measurement Accuracy | : | ±30 ppm ±3% of measured value |
| CO2 Measurement Range | : | 0 to 2000/5000 ppm (selectable) |
| CO2 Measurement Repeatability | : | ±20 ppm ±1% of measured value |
| CO2 Measurement Resolution | : | 1 ppm |
| CO2 Response Time | : | <60 seconds for 90% step change |
| CO2 Sensor Type | : | Non-dispersive infrared (NDIR), diffusion sampling |
| Collection | : | Plant Room Air Quality Sensors |
| Dimension Depth | : | 2" (51 mm) |
| Dimension Height | : | 3.95" (100.4 mm) |
| Dimension Probe Length | : | 7.8" (197 mm) |
| Dimension Width | : | 5.3" (133 mm) |
| Display Resolution | : | CO2: 1 ppm, Temp: 0.1 °C or °F, VOC: 1% AQI |
| Display Type | : | LCD, Positive Display with Backlight |
| Electrical Wiring Size | : | 24-16 AWG (.25-1.5 mm2) |
| Enclosure Material | : | Polycarbonate; flammability rating UL 94 V0 |
| IP Protection | : | IP65 |
| Input Specifications | : | Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz |
| Measurement Type | : | CO2 | VOC | Temperature |
| Measurement Values Displayed | : | CO2: ppm, Temp: °C or °F, VOC: AQI |
| Mounting | : | Duct |
| Operating Humidity | : | 0 to 95% RH, non-condensing |
| Operating Temperature | : | -25 to 70 °C (-13 to 158 °F) |
| Output Specifications | : | Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V |
| Outputs | : | Analog Output |
| Range | : | CD2 |
| Response Time | : | <60 seconds for 90% step change |
| Temperature Measurement Accuracy | : | ±0.2 °C (±0.4 °F) typical |
| Temperature Measurement Range | : | 0 to 50 °C (32 to 122 °F) |
| Temperature Measurement Resolution | : | 0.1 °C (0.1 °F) |
| Temperature Sensor Type | : | Solid state, integrated circuit |
| Terminal Blocks | : | Screwless terminal block with spring actuator, 16-24 AWG |
| VOC Measurement Accuracy | : | ±15% of measured value |
| VOC Measurement Range | : | 0 to 100% AQI for VOC |
| VOC Sensor Type | : | Solid state |
| Warranty | : | 5 years |
CD2 Series Air Quality Sensors are duct mount all-in-one sensors for monitoring air quality. The CD2 Series device combines CO2, temperature, humidity, VOC and particulate matter (PM) sensing into a single unit to ensure a building’s optimum air quality and energy efficiency. Each CD2LAXAVX device is an active sensor that converts a measurement into the following Analog output options: 4-20 mA, 0 to 5 Vdc or 0 to 10 Vdc