| Application Zone | : | Plant Room |
| Application | : | Duct Pressure Monitoring | Filter Monitoring | Fan Monitoring | VAV Control | Air Velocity Monitoring |
| Bluetooth Communication | : | No |
| Brand | : | Veris |
| Burst Pressure | : | 5 psid (34 500 Pa) |
| Calibration Certificate | : | NIST Certificate |
| Dimension Depth | : | 1.6" (42 mm) |
| Dimension Height | : | 4.4" (112 mm) |
| Dimension Probe Diameter | : | 0.3" (7 mm) |
| Dimension Probe Length | : | 7.4" (188 mm) |
| Dimension Weight | : | 4.4 oz (125 g) |
| Dimension Width | : | 3.5" (88 mm) |
| Display Type | : | None |
| Electrical Wiring Size | : | AWG 22 (35 mm²) |
| Electrical Wiring | : | 3-wires |
| Enclosure Material | : | ABS Plastic |
| Fitting Material | : | Brass |
| Fitting Size | : | 0.24" (6 mm) |
| Fitting Type | : | Male |
| IP Protection | : | IP65 (NEMA 4) |
| LED Indicator Type | : | RGB |
| Measurement Type | : | Differential Pressure |
| Medium | : | Air | Gas |
| Model | : | PX3DXN01S |
| Mounting | : | Duct |
| Operating Temperature | : | -4 - 140 °F (-20 - 60 °C) |
| Output Specifications | : | 4 - 20 mA | 0 - 5 V | 0 - 10 V |
| Outputs | : | Analog output |
| Pressure Measurement Accuracy | : | ±1% of F.S. |
| Pressure Measurement Range | : | 0.1"WC (25 Pa) | 0.25"WC (50 Pa) | 0.5"WC (100 Pa) | 1"WC (250 Pa) |
| Product Certification | : | CE |
| Product Type | : | Sensor |
| Range | : | PX3 |
| Standards EMC | : | EN 61000-6-3 | Class B | EN 61000-6-1 | EN61326-1 | EN61326-2-3 |
| Supply Voltage AC Nominal | : | 24 VAC |
| Supply Voltage DC Range | : | 12 - 30 VDC |
| Warranty | : | 5 years |
The PX3 transducer can measure either air pressure or velocity with the flip of a switch. PX3DXN01S Duct models has pressure and velocity of 0 to 1 in-WG / 0 to 3000 ft/min with four field-selectable subranges. The PX3 has an IP65/NEMA 4 environmental rating and a 5 years limited warranty.
For the bluetooth version, see PX3DXN01