| CO2 Measurement Accuracy | : | ±30 ppm ±3% of measured value | 
| CO2 Measurement Range | : | 0 to 2000/5000 ppm (selectable) | 
| CO2 Measurement Repeatability | : | ±20 ppm ±1% of measured value | 
| CO2 Measurement Resolution | : | 1 ppm | 
| CO2 Response Time | : | <60 seconds for 90% step change | 
| CO2 Sensor Type | : | Non-dispersive infrared (NDIR), diffusion sampling | 
| Color | : | Matte White | 
| Display Size | : | 2.05 in (52 mm) | 
| Display Type | : | Segmented LCD, with 3 Buttons | 
| Electrical Wiring Size | : | Screw terminals, 18-24 AWG | 
| Enclosure Material | : | High impact ABS plastic | 
| IP Protection | : | IP20 | 
| Input Specifications | : | Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz | 
| Measurement Type | : | CO2 / Temperature | 
| Operating Humidity | : | 0 to 95% RH non-condensing | 
| Operating Temperature | : | 0 to 50 °C (32 to 122 °F) | 
| Output Specifications | : | Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V | 
| Outputs | : | Analog | 
| Override | : | Yes | 
| Setpoint Range | : | Temperature: 0 to 50 °C (32 to 122 °F) / 10 to 35 °C (50 to 95 °F), selectable Fan Speed: Off, Low, Med., High. | 
| Setpoint Specifications | : | 0-10Vdc. Temperature or fan speed (one setpoint type is selectable via dip switch) | 
| Setpoint | : | Yes | 
| Standards EMC | : | EN61000 Series - industrial immunity | 
| Standards | : | CE, UL 916, RCM, ICES-003. REACH, RoHS | 
| Temperature Measurement Accuracy | : | ±0.2 °C (±0.4 °F) typical | 
| Temperature Measurement Range | : | 0 to 50 °C (32 to 122 °F) | 
| Temperature Measurement Resolution | : | 0.1 °C (0.1 °F) | 
| Temperature Sensor Type | : | Solid state, integrated circuit | 
| Warranty | : | 5 Years | 
The CW2LAXA is an analog multi sensor platform for use with various brands of BAS controllers designed to accept 4 to 20mA, 0 to 5Vdc, 0 to 10Vdc, and various thermistor outputs. The CW2 series sensors feature no-logo on the faceplate. CO2 and temperature sensors are included with all CW2 Series air quality sensors.