800.354.8556
+1 503.598.4564
  Search
Veris Industries
 
Order Summary

There are no items in the cart.
 
Onesource Rewards
Not logged-in or not enrolled in
Veris OSR.

Click here to Log In, or Click here for information about the Veris OSR program.
Customers also ordered
H8036-0100-2
Integrate 26 energy data points with the Enercept power meter
Home >

H8936

Modbus network display enclosed in a NEMA housing.

H8936 $1,732.15 EA
Quantity:



  • Overview
  • Series Specifications

The H8936 serves as the display tool for Modbus data. The H8936 is compatible with the H704, H663, H8238, Enercept®, E30, E31, E50Cx and E51Cx devices. It is enclosed in a box for easy installation.

APPLICATIONS

  • Allocating load-based costs
  • Managing loads
  • Overload protection
  • Collecting energy data
  • Tenant submetering

Easy to use

  • Large 1" x 4" backlit LCD with adjustable brightness control for easy viewing
  • Multi-color LED shows alarm status at a glance
  • Pass-through communications to other Modbus® devices
  • Easy keypad setup
  • Monitor a variety of Veris power transducers from a single location
  • AC Power Source Dedicated 120VAC, line-to-neutral. Fused. 200mA@250Vx20mm Fast-Blo
  • AC Power Voltage Tolerance (90-132VAC) for 120V
  • AC Power Frequency 50/60 Hz
  • AC Power Termination 2-position Euro-style pluggable connector (max wire size 12 gauge)
  • Alternate DC Power Source 12VDC, 300mA unfused (Auxiliary input disabled if line connected)
  • Operating Temperature Range 0° to 50°C (32° to 122°F); <95%RH, non-condensing
  • Storage Temperature Range -20°C to 70°C (-4° to 158°F)
Upstream Network Communications:
  • Interface RS-485, RS-232
  • Protocol Modbus RTU
  • Baud Rate UI-selectable 2400, 4800, 9600, 19200
  • Parity UI-selectable NONE, ODD, EVEN
  • Communication Format 8-data-bits, 1-start-bit, 1-stop-bit
  • RS-485 1/4-load transceivers; Duplex is UI-selectable 2-wire or 4-wire;5-position Euro-style pluggable connector
  • RS-232 DCE, no handshaking
  • DB-9 connection; pin 2: Transmitted Data from H8936; pin 3: Received Data into H8936; pin 5: Ground
Downstream Network Communications:
  • Interface RS-485
  • Protocol Modbus RTU
  • Duplex UI-selectable 2-wire or 4-wire
  • Load 1/4-load transceivers
  • Baud Rate UI-selectable 2400, 4800, 9600, 19200
  • Parity UI-selectable NONE, ODD, EVEN
  • Communication Format 8-data-bits, 1-start-bit, 1-stop-bit
  • Termination 5-position Euro-style pluggable connector UI-Switch Inputs Number/Function Four (METER, UP, DOWN, SELECT)
Auxiliary Input (Remote Alarm):
  • Type Contact closure or pull-to-ground (10mA max)
  • Isolation Optical to 2500VAC
  • Sense UI-selectable N.O. or N.C.; (i.e. Closed = Alarm or Open = Alarm)
LCD:
  • Size 1” x 4” visible area, 2 lines x16 characters per line
  • Backlight Green, UI-adjustable brightness in 10 steps