H8163-0100-0-1

Energy Meter, 100A, One micro CT, 120-480 VAC, pulse and phase loss output.

H8163-0100-0-1 $1,118.74 EA
Quantity:



  • Overview
  • Series Specifications
The H8163 Series Energy Meters are easy to install and provide exceptional system accuracy, making them ideal for all submetering applications. Each meter is factory-matched with one to three split-core CTs. Matching serial numbers assure that the meter and CT were calibrated together. The meter/CT pairs are system-calibrated to provide excellent total system accuracies of 1% from 2% to 100% of the amperage rating of the CTs (e.g., 2-100 amps with 100 amp CTs).

APPLICATIONS
  • Commercial tenant submetering
  • Performance contracting
  • Allocating costs
  • Real-time power monitoring via local display or through control/data acquisition systems
The ultimate stand-alone energy metering system
  • High resolution backlit LCD display provides clear readings at a distance...reduces the risk of misinterpretation of the data. Back-lighting can be disabled if desired
Easy integration to control or data acquisition systems
  • Pulse output from 1/10 to 1 pulse per kWh for easy connection to existing control systems
  • Phase-loss alarm...protects equipment
  • With the optional Communications Board, the EME can easily be added to a Modbus, BACNet or N2 control system network to report multiple variables including kW, kWh, kVAR, PF, Amps and Volts, providing crucial power information at a reduced installation cost
Simple, fast installation
  • Split-core CTs eliminate the need to remove electrical conductors...reduces installation time
  • Energy meters automatically detect and correct phase reversal, eliminating the need to be concerned with CT load orientation
  • CTs and voltage leads are color coded making it easy to determine correct connection
  • Voltage Tolerance 90 - 300VAC line-to-neutral
  • Electrical Services Any service where the phase A-N voltage is =300VAC & the phase-to-phase voltage is < 480VAC nom, with neutral
  • Power Consumption 50VA
  • Insulation Class 600VAC†
  • Internal Isolation 2500VAC
  • LCD Display 1.2" (31mm) x 3.8" (97mm) viewing area, 160 segments, back-lit with green LEDs
  • Sample Rate 1280Hz
  • Operating Temp. Range 0° to 50°C (32° to 122°F) (<95%RH, non-condensing)
  • Storage Temp. Range -40° to 70°C (-40° to 158°F)
  • Systems Accuracy ±1% of reading from 2% to 100% of the rated current of the CTs, accomplished by matching the CTs with a meter and calibrating them as a system
  • Frequency 50/60Hz
  • Pulse Output N.O., Opto-FET, 100mA @ 24VAC/DC
  • Pulse Rate 0.10*, 0.25**, 0.50, or 1.00 kWh per pulse
  • Pulse Width 200msec closed
  • Phase Loss Alarm Output N.C., Opto-FET, 100mA @ 24VAC/DC; Fixed threshold 25% below any other phase. Always open as long as alarm persists
  • Protection Class NEMA 1

*not supported at >1600A**not supported at >2400A†Do not apply 600V Class current transformers to circuits having a phase-to-phase voltage greater than 600V, unless adequate additional insulation is applied between the primary conductor and the current transformers. Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.Note: Meter and CT serial numbers must match