Energy Meter, 200A, Two mini CTs, 120 VAC L-N, display only.

H8150-0200-1-2 $1,432.44 EA
Quantity:



  • Overview
  • Series Specifications
The H8150 Series Energy Meters are easy to install and provide exceptional system accuracy, making them ideal for all submetering applications. Each meter is factory-matched with one to three split-core CTs. Matching serial numbers assure that the meter and CT were calibrated together. The meter/CT pairs are system-calibrated to provide excellent total system accuracies of 1% from 2% to 100% of the amperage rating of the CTs (e.g., 2-100 amps with 100 amp CTs).

APPLICATIONS
  • Commercial tenant submetering
  • Performance contracting
  • Allocating costs
  • Real-time power monitoring via local display or through control/data acquisition systems
The ultimate stand-alone energy metering system
  • High resolution backlit LCD display provides clear readings at a distance...reduces the risk of misinterpretation of the data. Back-lighting can be disabled if desired
Simple, fast installation
  • Split-core CTs eliminate the need to remove electrical conductors...reduces installation time
  • Energy meters automatically detect and correct phase reversal, eliminating the need to be concerned with CT load orientation
  • CTs and voltage leads are color coded making it easy to determine correct connection
  • Voltage Tolerance 90 - 132VAC line-to-neutral
  • Electrical Services 120/240 VAC with neutral, 208Y/120 VAC line to neutral
  • Power Consumption 50VA
  • Insulation Class 600VAC†
  • Internal Isolation 2500VAC
  • LCD Display 1.2" (31mm) x 3.8" (97mm) viewing area, 160 segments, back-lit with green LEDs
  • Sample Rate 1280Hz
  • Operating Temp. Range 0° to 50°C (32° to 122°F) (<95%RH, non-condensing)
  • Storage Temp. Range -40° to 70°C (-40° to 158°F)
  • Systems Accuracy ±1% of reading from 2% to 100% of the rated current of the CTs, accomplished by matching the CTs with a meter and calibrating them as a system
  • Frequency 50/60Hz
  • Protection Class NEMA 1

*not supported at >1600A**not supported at >2400A†Do not apply 600V Class current transformers to circuits having a phase-to-phase voltage greater than 600V, unless adequate additional insulation is applied between the primary conductor and the current transformers. Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.Note: Meter and CT serial numbers must match