800.354.8556
+1 503.598.4564
  Search
Veris Industries
 
Order Summary

There are no items in the cart.
 
Onesource Rewards
Not logged-in or not enrolled in
Veris OSR.

Click here to Log In, or Click here for information about the Veris OSR program.
Customers also ordered
GWN1XX
Gas,Platform, Wall Mount, Hi/Lo/End of Life, relay only (requires sensor module)
GWNMXX
Gas,Platform, Wall Mount, Hi/Lo/End of Life,4-20mA (requires sensor module)
GWNVXX
Gas,Platform, Wall Mount, Hi/Lo/End of Life, 0-5/0-10vDC (requires sensor module)
Home >

AG04

CO NO2 Combination, Sensor Module, GWNP Series, CO Sensor: 0-500ppm range, default set-points 25 low, 180 high, adjustable from 0 to top of range. ±5% accuracy. NO2 Sensor: 0-5ppm range, default set-points 1 low, 3 high, adjustable from 0 to top of ran

AG04 $557.76 EA
Quantity:



  • Overview
  • Series Specifications

GWNP Series carbon monoxide sensors maximize energy savings, while ensuring optimal ventilation. The sensors allow ventilation systems to be controlled by the amount of CO and NO2 present in a location. The GWN Series detects fluctuations in CO and NO2 levels, and it signals air systems to provide an inlet of fresh air optimal for the space at a given time. In this manner, the ventilation fan does not need to run continuously, saving energy and reducing maintenance costs. The GWNP Series uses replaceable AG Series sensor modules.

APPLICATIONS

  • Ensuring OSHA air quality compliance in commercial buildings and factories

High accuracy and stability

  • Microprocessor controlled...high accuracy, excellent stability
  • No calibration required...easy maintenance and worry-free operation
  • Sensor, Electrochemical

Ventilation control in parking garages for energy savings

  • 2-year warranty, long-life replaceable sensor element
  • Use with GWNP Series platform
  • Sensors: CO: Electromechanical, NO2 Electromechanical
  • Detection Range CO 0 to 500 ppm, NO2 0-5ppm
  • Accuracy: CO +/-5%, NO2 +/-5%
  • Resolution: 1 ppm
  • Low Limit Setpoint: CO Adjustable (25ppm default), NO2 Adjustable (1ppm default)
  • High Limit Setpoint: CO Adjustable (180ppm default), NO2 Adjustable (3ppm default)
  • End of sensor warranty indication
  • Operating Environment -20° to 40°C (-4° to 104°F); 0 to 90% RH non-condensing