LDRA6 control panels continuously monitor up to 1,000 ft. of SC water detection cable per zone. If the cable detects conductive fluid at any point along its length, the detection panel illuminates the corresponding zone LED, clearly indicating which zone is affected. An alarm signals the presence of a leak. Additionally, if the cable fails or loses continuity, the panel will activate a cable fault LED. The detection sensitivity can be set independently for each zone. A summary alarm relay output is standard. The LDRA6 can interface with a computer via an RS-232 port, through which 117 days of cable current level readings and the last 100 alarms can be accessed for analysis. The LDRA6-MB also offers an optional Modbus® slave port allowing other devices to communicate with it.
APPLICATIONS
  • Monitoring data centers, computer room under-floor areas, mechanical rooms, and electrical control centers
  • Protecting records storage rooms
  • Monitoring plumbing in facilities
  • Monitoring chilled beams
Features
  • Monitor up to 1,000 ft. (300m) of water leak detection cable per zone...application flexibility
  • Two LED indicators per zone...leak and cable fault
  • Sensitivity settings for each zone help eliminate false alarms...maximum detection accuracy
  • Summary alarm relay output...fast response
  • Alarm and trend logs of the last 100 alarms and 117 days of cable current levels, plus RS-232 and Modbus RS-485 ports...output versatility
  • Input Power 24VAC/DC (±10%) @ 600mA max.
Inputs:
  • Water Leak Detection Cable Requires 15ft. (4.5m) leader cable kit (LC-Kit) per zone
  • Maximum Cable Length 1000 ft. (305m)
  • Detection Response Time 20-3600sec, software adjustable in 10 sec increments, ±2%
  • Relay Output 1 Form C summary alarm relay, 1 Form C relay for each zone/alarm; 1A@24VDC, 0.5 resistive @120VAC
Communication Ports:
  • RS-232 & RS-485 1200, 2400, 9600, or 19200 selectable; no parity; 8 data bits, 1 stop bit
  • Terminal Emulation (RS-232) VT100 Compatible (configuration)
  • Modbus (RS-485) (LDRA6-MB only) Slave; RTU Mode; Supports function codes 03, 04, 06 and 16
  • Alarm Notification Audible Alarm 85dBA@2 ft. (0.6m) re-sound disabled, 8, 16, or 24 hrs.
  • Push Buttons 1 for reset, quiet, and test
Operating Environment:
  • Temperature 0° to 50°C (32° to 122°F)
  • Humidity 5% to 95% RH, non-condensing
  • Altitude 15,000 ft. (4,572m) max
  • Storage Environment -20° to 70°C (-4° to 158°F)
  • Weight 4 lbs. (2 kg)
  • Certifications CE; ETL Listed; Conforms to UL 61010-1, EN 61010-1, CAN/CSA C22.2 No. 1010.1, RoHS Compliant