Veris Homepage  
 
800.354.8556 / +1.503.598.4564
 
  Search
[Login]
Order Summary

There are no items in the cart.
 
Home >
HED3JSTH-V1
HED3JSTH-V1 - (OBSOLETE)
Contact sales representative for availability.
  • Overview
  • Series Specifications

This part is being discontinued and is available through February 2012.  The new replacement for this part uses the same part number* but does not have the -V1 suffix.  The new series of economy RH products is currently available.

* 0-5V "J" voltage option models are not in the new part lineup as the new "V" voltage option models are 0-5/0-10V selectable. 

HED Economy Series humidity transmitters offer an array of humidity control solutions at an affordable price. All devices include embedded electronics to protect against condensation. The thin-film capacitive sensor elements provide high accuracy and performance. The duct mounted HED includes a sturdy sheet metal housing. All Economy models come with a standard one-year warranty.

APPLICATIONS

  • Managing energy systems
  • HVAC economizer control
  • Facilitating ASHRAE standards for environmental control

Reduce Installation Costs with Combination Sensors

  • Monitor humidity and temperature with a single device
  • Circuitry is embedded in the probe for durability and protection

This part is being discontinued and is available through February 2012.  The new replacement for this part uses the same part number* but does not have the -V1 suffix.  The new series of economy RH products is currently available.

* 0-5V "J" voltage option models are not in the new part lineup as the new "V" voltage option models are 0-5/0-10V selectable. 

  • Input Power 12 (15 for 0-10V) to 30VDC/24VAC, 15mA max.
  • HS Element Digitally profiled thin-film capacitive, non removable
  • Accuracy at 25°C from 10-90% RH ±3%
  • Reset Rate* 24 hours
  • Stability ±1% @ 20°C (68°F) annually, for two years
  • Operating Humidity Range 0 to 100% RH (non-condensing)
  • Temperature Effect (0.0015%RH(T°C-25))+(%RH0.0008abs(T°C - 25))
  • Analog Output 0-5V, 3-wire, observe polarity
  • Scaling 0–100% RH
  • Operating Temperature Range -40° to 50°C (-40° to 122°F)


1-year limited warranty*Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.One side of transformer secondary is connected to signal common. Isolation transformer, or dedicated power supply may be required