Split core, amperage range: 0 to 30/60/120A AC selectable, Analog output transducer: 4-20mA loop powered output and SPST N.O. integral command relay with 24VAC/DC coil, LED status. UL.

H931 $177.10 EA
Quantity:


  • Overview
  • Series Specifications
he Hawkeye 931 provides accurate load trending information with a proportional 4-20mA output signal. This device offer three amperage ranges for versatility, with easy slide-switch selection. The command relay is fully integrated in the device, but it is isolated from the current sensor. This combination makes these products ideal for start/stop control and status monitoring of motors, using one device instead of two.
APPLICATIONS
  • Load trending
  • Motor control
  • Positive proof of flow
Loop-powered analog current sensor with integral start/stop command relay
  • Reduces the number of installed components...saves time and space
  • Self-gripping split-core for fast retrofit installation...no need to remove conductor
  • One device to install for start/stop & status...reduces installation charges
  • Power the current sensor and receive the 4-20mA signal with only two wires...fewer wires required than with traditional 3-wire sensors
Selectable factory calibrated ranges up to 120A for increased flexibility and resolution
  • Factory calibrated switch-selectable ranges (30/60/120A) for high resolution and installation ease
  • No jumpers on unit...reduce installation error
  • Removable mounting bracket for installation flexibility
  • Bracket can be installed in three different configurations...added flexibility
  • Command relay switches up to 5A@250VAC
  • 5-year limited warranty
  • Sensor Power 30mA (max.)@12-30VDC
  • Insulation Class 600VAC RMS
  • Frequency Range 50/60Hz
  • Temperature Range -15° to 60°C (5° to 140°F)
  • Humidity Range 10 - 90% RH, non-condensing
  • Accuracy ±2% full scale from 10% to 100% (selected range)
  • Response Time 2 sec.
  • Terminal Block Maximum Wire Size 14 AWG
  • Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
  • Agency Approvals UL 508 open device listing

Do not use LED status indicators as evidence of applied voltage