  • Overview
  • Series Specifications
The Hawkeye 723 Series provides accurate load trending information with a proportional 0-10VDC output signal. Devices offer three amperage range options, with slide-switch selection for easy field adjustment – no need for jumpers.
APPLICATIONS
  • Load trending
  • Motor control
  • Fan/pump status
Self-powered analog current sensor, 0-10VDC output
  • No jumpers on unit...reduces installation error
  • No external power required for sensor
Factory calibrated for ease of installation
  • Factory calibrated field-selectable ranges for high resolution and installation ease
  • One device to stock and install...reduces installation charges
  • Removable mounting bracket for installation flexibility
  • 100% solid state, no moving parts to fail
  • 5-year limited warranty
  • Sensor Power Induced from monitored current
  • Insulation Class 300VAC RMS
  • Frequency Range 50/60Hz
  • Temperature Range -15° to 60°C (5° to 140°F)
  • Humidity Range 10 - 90% RH, non-condensing
  • Accuracy ±2% full scale from 10% to 100% (selected range)
  • Response Time 2 sec.
  • Terminal Block Maximum Wire Size 14 AWG
  • Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
  • Agency Approvals CE: EN61010-1:2001-2, CAT III, deg. 2, basic insulation

For applications requiring double or reinforced insulation, please contact the factory