Hawkeye 706 current switches provide accurate, reliable, and maintenance-free fan and pump status indication.
APPLICATIONS- Monitoring fans, pumps, motors, and other electrical loads for proper operation
- Detecting belt loss and motor failure...ideal for fan and pump status
- Verifying lighting circuit loads
- Monitoring critical motors (compressor, fuel, etc.)
- Monitoring industrial process equipment status (OEM)
Cost effective...reduced installation and service costs- Adjustable trip point...4 amperage range options for versatility
- Easier to install than differential pressure switches...no tubing needed
- 100% solid-state, no moving parts to fail
- Output status LEDs for fast setup
- 5-year limited warranty
- Sensor Power 5-30VDC
- Insulation Class 600VAC rms (UL), 300VAC RMS (CE)
- Frequency Range 50/60Hz
- Temperature Range -15° to 60°C (5° to 140°F)
- Humidity Range 10-90% RH, non-condensing
- Hysteresis 10% Typical
- Off State Leakage 34µA@5VDC, 200µA@30VDC
- On State Voltage Drop 1.9VDC max@0.1A
- Terminal Block Maximum Wire Size 14 AWG
- Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
- Agency Approvals UL 508 open device listing CE: EN61010-1:2001-02, CAT III, deg. 2, basic insulation
Do not use the LED status indicators as evidence of applied voltageFor applications requiring double or reinforced insulation, please contact the factory.