The E50H5 BACnet MS/TP DIN Rail Meter with Data Logging combines exceptional performance and easy installation to deliver a cost-effective solution for power monitoring applications. Native serial communication via BACnet MS/TP provides complete accessibility of all measurements to your Energy Management system   The data logging capability protects data in the event of a power failure. The E50H5 can be easily installed on standard DIN rail, surface mounted or contained in an optional NEMA 4 enclosure, as needed. The front-panel LCD display makes device installation and setup easy and provides local access to the full set of detailed measurements.  Two pulse inputs provide an easy way to incorporate simple flow sensors to track gas, water, steam, or other energy forms using a BACnet building automation system in addition to full monitoring of electrical energy.

APPLICATIONS

  • Energy monitoring in building automation systems
  • Energy management
  • Commercial submetering
  • Industrial monitoring
  • Cost allocation

FEATURES

  • DIN rail mounting option...easy installation
  • ANSI 12.20 0.5% accuracy, IEC 62053-22 Class 0.5S...great for cost allocation
  • Real energy output and phase loss alarm output...one device serves multiple applications
  • 90-600 VAC...application versatility with fewer models to stock
  • Bright backlit LCD...easy visibility in dark enclosures
  • Data logging capability...safeguard during power failures
  • Compatible with CTs from 5A to 32000A...wide range of service types
  • User-enabled password protection...protect from tampering
  • System integration via BACnet MS/TP...convenient compatibility with existing systems
  • Native BACnet MS/TP support (no gateway) with serial rates up to 115.2 kbaud (E50H5)

Inputs:

  • Control Power, AC: 50/60 Hz; 5VA max.; 90V min.; UL Maximums: 600V L-L (347V L-N ); CE Maximums: 300V L-N (520V L-L )
  • Control Power, DC: 3W max.; UL and CE: 125 to 300VDC (external DC current limiting required)
  • Voltage Input: UL: 90 V L-N to 600 V L-L ; CE: 90 V L-N to 300 V L-L
  • Current Input
  • Scaling: 5 A to 32,000 A
  • Input Range: 0 to 0.333 V or 0 to 1 V (selectable)
  • Pulse Inputs: Two sets of contact inputs to pulse accumulators

Accuracy:

  • Real Power and Energy 0.5% (ANSI C12.20, IEC 62053-22 Class 0.5S)

Outputs:

  • Serial Communication: RS-485 2-wire BACnet MS/TP (9600 baud to 115.2 kbaud)

Mechanical:

  • Mounting: DIN Rail or 3-point screw mount, NEMA 4 enclosure optional

Environmental:

  • Operating Temperature Range: -30° to 70°C (-22° to 158°F)
  • Storage Temperature Range: -40° to 85°C (-40° to 185°F)
  • Humidity Range: <95% Relative Humidity, noncondensing