E34E04 $1,548.00 EA
Quantity:


  • Overview
  • Series Specifications

The E34E Ethernet Series Multi-Circuit Power Meter provides a flexible cost efficient solution to monitoring multiple meters. With a single device, and a relatively small space, it is possible to install from four 3ph (or 12 single phase) meters, up to twenty-eight 3ph (or 84 single phase) meters. E34E will monitor current, voltage, power and harmonic distortion (THD). This enables a user to allocate energy cost and have basic power quality monitoring to improve efficiency and identify potential early wear and tear through the harmonics. 

APPLICATIONS

  • Commercial and residential sub-tenant billing
  • Multi-dwelling units
  • Load-based cost allocation
  • Overload protection
  • Energy management

FEATURES

  • ANSI & IEC Class 0.5% accuracy, ideal for tenant billing
  • Low equipment and installation cost per metering points
  • Possibility to assign measurement channels as needed for the site: each channel can be assigned to a 3ph, 2ph or single phase meters. EG: A (4) 3ph meter E34, can be a (4) 3ph meter, (8) 2ph meter, (12) single phase, or any mix like (1) 3ph with Neutral + (1) 3 ph + (2) 2ph + (1) 1ph meters which amounts to 12 channels equivalent to (4) 3ph meters.
  • Space saving size fits most electrical cabinets
  • Low voltage Current Transformers (CTs) offer a safer and more accurate alternative to 5A CTs and shorting blocks
  • Communications: The addition of Ethernet allows concurrent use of multiple protocol allowing E34E to report simultaneoulsy to an Energy Management System (EMS), Building Management System (BMS) or an IT network monitoring system 
    • Serial: Modbus RTU
    • Ethernet: BACnet MS/TP, Modbus TCP/RTU, BACnet IP and SNMP

Voltage Inputs

  • Measurement Voltage: 90 to 300 Vac line-to-neutral, 50/60 Hz
  • Control Power: 100 to 277 Vac line-to-neutral, 50/60 Hz, 15VA

Accuracy

  • Power/Energy: IEC 62053-21 Class 0.5, ANSI C12.20 class 0.5
  • Voltage: ±0.5% of reading 90 to 277 V line-to-neutral
  • Current: ±0.5% of reading from 2% to 100% full scale

Operation

  • Sampling Frequency: 2560 Hz
  • Update Rate: 2 seconds (both panels)
  • Overload Capability: 22 kAIC

Serial Communication

  • Physical Interface: 2-wire RS-485
  • Protocols Supported: Modbus RTU or BACnet MSTP
  • Address Range: 1 to 247 for Modbus RTU; 0-127 for BACnet MS/TP
  • Baud Rate: 9600, 19200, 38400
  • Parity: Modbus RTU: NONE, ODD, EVEN BACnet MS/TP: NONE (fixed)

Ethernet Communication

  • Physical Interface: Rj45 connector with 10/100 Mbit Ethernet
  • Protocols Supported: Modbus TCP, BACnet IP, SNMP V2c

Terminal Block Torque

  • Removable Connectors: 4.4 to 5.3 in-lb (0.5 to 0.6 N-m)

Operating Conditions

  • Operating Temp Range: 0 to 60°C (32 to 140°F) (<95% RH non-condensing)
  • Storage Temp Range: -40 to 70°C (-40 to 158°F)
  • Altitude of Operation: 3000 m
  • Mounting Location: Indoor use, dry location

Warranty

  • Limited Warranty: 5 years

Compliance Information

  • Agency Approvals: IEC/EN61010-1
  • Installation Category: Cat III, pollution degree 2