The CWE are non-dispersive infrared (NDIR) analyzers designed for measuring environmental CO2 concentration in ventilation systems and indoor living spaces. Their measurement range of 0-2000ppm makes them compliant with ASHRAE and other standards for ventilation control. The CWE Series provides a user-selectable 4-20mA or 0-10VDC output for versatility. Microprocessor-based digital electronics and a unique self-calibration algorithm improves long-term stability and accuracy.
APPLICATIONS- Controlling ventilation in response to occupancy
- Facilitating compliance with ASHRAE 62.1-2004 standard for air quality
- Office buildings, conference rooms, schools, retail stores, etc.
Microprocessor design increases accuracy and reduces installation time- Non-dispersive infrared technology repeatable to ±20 ppm ±1% of measured value
- Innovative self-calibration algorithm...easy to maintain
- 5-year calibration interval (recommended)
- Low ambient sensitivity
- Alarm relay with setpoint for direct ventilation control
- Output 4-20mA/0-10V for flexible control system interface
- 3-year factory warranty from date of purchase
- Input Power 20 to 30VDC/24AC; 100mA Maximum
- Analog Output 4-20mA, (clipped and capped)/0-10VDC (selectable)
- Operating Temperature Range 0° to 50°C (32° to 122°F)
- Housing Material High impact ABS plastic
- Sensor Type Non-dispersive infrared, diffusion sampling
- Measurement Range 0-2000 ppm
- Accuracy ±30 ppm ±2% of measured value*
- Repeatability ±20 ppm ±1% of measured value
- Response Time <60 seconds for 90% step change
EMC Conformance: EN 61000-6-3:2001 Class B, EN 61000-6-1:2001, EN 61000-3-2:2000, EN 61000-3-3:2001, EMC Test Methods: CISPR 22:1997 (Amended A1:2000, A2:2002) Class B, IEC 61000-4-2:2002, IEC 61000-4-3:2006, IEC 61000-4-4:2004, IEC 61000-4-5:2001, IEC 61000-4-6:2004, IEC 61000-4-8:2001, IEC 61000-4-11:2004.EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2001 specification requirements).*Measured at NTP